Text preview for : OA01GB09.PDF part of APC DP300E User Manual APC DP300E



Back to : OA01GB09.PDF | Home

DATAPOWERTM
DP300E Series User guide

Copyright © 1997 Silcon Power Electronics A/S Due to continuous product development information given in this manual is subject to change without notice.

7OA0001 GB rev.09

User Guide DP300E

1

7OA0001 GB rev.09

2

User Guide DP300E

Contents:
1.0
1.1 1.2

Introduction
General The display unit

2.0
2.1 2.2 2.3

Stop-start
General Stop Start

3.0
3.1

Operation
Keyboard description

4.0
4.1 4.2

Programming parameters
General Parameters

5.0 6.0
6.1 6.2 6.3 6.4 6.5

Reading out measurements Alarms - what to do
General The events stack Alarm messages The events logger Displaying the events stack

7.0
7.1 7.2

Service bypass switch
Operating the external service bypass switch Operating the external service bypass switch for parallel systems

8.0
8.1 8.2 8.3 8.4

Preventive maintenance
General Fan Battery Battery capacity test

9.0

Economy operation

10.0 Software
10.1 10.2 10.3 Choice of software Configuration codes Choice of cable

11.0 How to contact Silcon
7OA0001 GB rev.09

User Guide DP300E

3

Introduction
1.0
1.1

Introduction
General

Congratulations on your choice of UPS (Uninterruptible Power Supply). This UPS has been designed and produced for reliable and troublefree long-term use. For you it means that once installed and commissioned, you can forget it. You only have to arrange a preventive maintenance as described in section 8 of this manual.

1.2

The display unit

The display unit ­ placed on the front of the UPS ­ is the link between user and UPS. It consists of a display, an alarm LED, and a keyboard. The display is used for showing parameters, measured values, and alarm messages. A background light is activated in case of an alarm or if one of the keys are pressed. No activity or no alarm for 5 minutes will automatically switch of the light. By pressing pressing and and simultaneously you increase the contrast, and by simultaneously you decrease the contrast.

Note: The display accuracy is ±1%, ±1 digit.

The alarm LED is together with an acoustic signal the indicator for unusual operating situations. The light changes from green to red in case of alarm. The keyboard is used for programming of operating parameters and for calling readouts of parameters / alarm messages.

7OA0001 GB rev.09

4

User Guide DP300E

Stop ­ start
2.0
2.1

Stop ­ start
General

According to electrical regulations only the local authorized electrical installer is normally allowed to perform a complete switching in and out of the UPS, as it involves operation of the battery supply breaker, where touch of high voltage parts is possible. For above reasons the normal user can only switch the UPS into system off mode and from here back into normal operation via the "safe" push buttons.

2.2 Warning: Please read maintenance section, if UPS has to be stopped for more than one week.

Stop Display shows
System off

Action
Open the front door and activate the "ON" and "OFF" push-button simultaneously

Description
Alarm LED lights. Acoustic alarm sounds for 30 seconds.

2.3

Start Display shows
Normal operation Load power xx%

Action
Open the front door and activate the green "ON" push-button

7OA0001 GB rev.09

User Guide DP300E

5

Operation
3.0 Operation

The display is used to show parameters, alarms/messages, and measured values. The alarm LED is used with an audible alarm to indicate unusual operating situations. The keyboard is used for programming and control of displaying parameters, alarm messages, and displaying measured values.

3.1

Keyboard description

7OA0001 GB rev.09

6

User Guide DP300E

Programming parameters
4.0
4.1

Programming parameters
General

Some operating parameters can be programmed directly from the keyboard, but this has already been done during the commissioning. Unless you are quite sure of the consequence of changing the following parameters, then let it be a task for your local dealer, if needed. Parameters are programmed as shown in the example 4.2.3.

4.2 4.2.1

Parameters

Parameter

Setting* YES, NO GB, D, F, DK, S, SF NL, PL, CZ E, P, SK, H YES, NO YES, NO

Comments "YES" will switch the system into bypass mode Language of text in display

NOTE: The system must not run in bypass mode for longer periods of time as the batteries will not be recharged

Bypass Language

Autostart Remote shutdown active Remote shutdown Remote shutdown time

Automatic restart by mains return. Ensures quick battery recharge. Shutdown of UPS by remote signal

HIGH, LOW Nature of remote shutdown signal polarity 0, 1, 2, 3, 4 5, 6, 7, 8, 9 10 min. Time delay on remote shutdown of UPS

Battery capacity test

Initiates check of back-up time. The measured time is from start until it reaches low DC warning level (See section 8.4) Initiates check of battery condition by 25% discharging. Activates the battery monitor test in cyclic intervals (Unit - months) and key after Pressing the selecting this parameter resets alarms and flushes messages in the alarm stack "YES" results in boost charge (10 hours) "YES" results in boost charge after battery operation (10 hours) Local date can be entered Local time can be entered

Battery monitor test** Automatic battery test** Battery monitor reset**

NO, 3, 6 -

Boost charge Autoboost charge Enter new date Enter new time

YES, NO YES, NO YYMMDD HHMMSS

* Text in bold letters are the standard setting ** Only for systems with Battery Monitor active

7OA0001 GB rev.09

User Guide DP300E

7

Programming parameters
4.2.2 Keys used for programming

4.2.3 Programming example - switch to bypass operation
Action 1. Press 2. Press 3. Press 4. Press to enter parameter stack or until to store until Display shows

Bypass operation : NO
Bypass operation : YES

To return to normal operation Action 5. Press 6. Press 7. Press 8. Press 9. Press to enter parameter stack or until to store to exit Normal operation load power xx% until Bypass operation : YES Bypass operation : NO Display shows

Programming of the other parameters can be performed in exactly the same way.
7OA0001 GB rev.09

8

User Guide DP300E

Measurements
5.0 Reading out measurements

Press as indicated below one key or two keys simultaneously (Used values are only random for illustration): Action Display shows 96.04.16 10.22,13 Mains voltage 385 385 385 Vac Mains Current 16 16 16 Aac Battery voltage 438 437 Vdc Battery current + 2 Adc Output voltage 380 380 380 Vac Output current 15 15 15 Aac Output frequency 50Hz Battery temp. 25ºC
Output peak current 22 22 22 Aac

Description Year, month, day Hour, minute, second Mains voltage is 3 x 385 Vac Mains current is 3 x 16 Aac Battery voltage is 438 Vdc on batt.1. 437 Vdc on batt.2. Charging current is (+) 2 Adc (Discharging current (÷)) Output voltage is 3 x 380 Vac Output current is 3 x 15 Aac Output frequency is 50 Hz Battery temperature is 25°C Output peak current is 3 x 22Aac (only of interest for service engineers) Returns to normal status indication. If not pressed, automatic switch back will be performed after 20 seconds.

Normal operation load power xx%

7OA0001 GB rev.09

User Guide DP300E

9

Alarms
6.0
6.1

Alarms - What to do
General

Alarms are indicated by the red lamp (above the upper left corner of the keyboard) and by a 30 secs. acoustic signal. An alarm is registered in an alarm stack as long as it is present, and if more in the same succession as they arise.

6.2

The alarm stack
Description Access to the alarm stack

The alarm stack can be displayed by: Action 1. Press

2. Press

or

Scroll up or down through the alarm stack messages. Last message is "No (further) alarm". Exits the alarm stack. If not operated the system will exit the alarm stack automatically after 30 seconds.

3. Press

6.3

Alarm messages

The alarm messages are together with the events logger (described in section 7.0) part of a diagnostic system for the UPS service specialist. Before calling for assistance you may take one or more of the following actions. 1. "Battery defective" means no back-up capacity any longer. Call for assistance. "Battery Week" means reduced back-up capacity. Reset the "Battery week" alarm signal according to point 4.2 and start up a battery capacity test according to point 8.4. When finished ­ record the obtained back-up time and reset an eventual new alarm from the battery monitor. Let the UPS recharge the battery for at least 16 hours, and with the same load as before start up a second battery capacity test. If this results in improved back-up time continue with further capacity tests until none or insignificant improvements take place. Above might "wake up" the battery ­ else call for assistance. Check the local mains power supply. One or more fuses may be blown or somebody could by accident have switched off the supply. Check if the cooling air intake on your UPS has been blocked. Check if somebody has switched more load on the UPS - the max. output capacity may be exceeded. If there is no output voltage from the UPS - the mains supply is present and atempt to restart gives no result ­ bypass the UPS as described in the following section by means of the external service bypass switch if present.

NOTE: A battery monitor test can not be performed unless the battery is fully charged.
2.

3. 4.

5.

7OA0001 GB rev.09

10

User Guide DP300E

Alarms
6.4 The events logger
The events logger is a memory stack, in which the last 250 events are stored in the same succession as they arose. (Showing the latest at first). Events stored are the alarms and the following operational modes: Mode MPU is reset Stand-by Normal operation Battery operation Bypass operation System off Comments UPS has been totally switched off UPS has been in stand-by mode by parallel system UPS has been in normal operation UPS has been in battery operation UPS has been in bypass operation UPS has been off

6.5

Displaying the events stack
Description and or Press the two keys simultaneously to get access to the events stack Scroll up or down through the events stack (last message is "No (further) event"). Displays the time where the event happened

Action 1. Press 2. Press

3. Press

4. Press

Exit the events stack. If not operated the system will exit the events stack automatically after 30 seconds

7OA0001 GB rev.09

User Guide DP300E

11

Service Bypass Switch
7.0
7.1
7.1.1

Service bypass switch
Operating the external service bypass switch
Bypassing the UPS

DP

Action Display shows Bypass operation : NO Bypass operation : YES

1. 2. 3. 4.

Press Press Press Press

on the keyboard or on the keyboard until

on the keyboard on the keyboard

Lamp indication on bypass panel 5. Check lamp indication on the bypass panel The Green lamp (H003) above the bypass switch handle (Q003) lights The Green lamp (H002) above the output switch handle (Q002) lights Only the lamp (H002) above the output switch handle (Q002) lights now Display shows 8. Open the front door and press both the green ,,ON" and the red ,,OFF" key simultaneously The acoustic alarm sounds for 30 secs.* **System OFF**

6.

Turn the external bypass switch (Q003) to position ,,1".

7.

Turn the output switch (Q002) to position "0".

Warning: If the UPS is out of service for more than 8 days the connected batteries might be damaged. Refer to total ,,Switching off" as described in the Installation Guide.

9.

Turn the input switch to position ,,0". The red alarm LED below the display lights and the acoustic alarm sounds for 30 secs.

* The acoustic alarm can be reset by the

key

EMERGENCY (UPS not alive) 1. 2. 3. 4. Turn the input switch (Q001) to position ,,0". Turn the output switch (Q002) to position ,,0". Change released system input fuse(s), if any. Turn the bypass switch (Q003) to position ,,1".

7OA0001 GB rev.09

12

User Guide DP300E

Service Bypass Switch
7.1.2 Switching the system from external bypass into normal UPS operation

DP

Action* 1. Turn the input switch (Q001) to position ,,1" Open the UPS front door and press the green ,,ON" key Press Press Press Press on the keyboard or on the keyboard until

Display shows **System OFF** Normal operation load power 0%

2.

3. 4. 5. 6.

Bypass operation : NO Bypass operation : YES

on the keyboard on the keyboard

Lamp indication on bypass panel 7. Check lamp indication on the bypass panel The Green lamp (H002) above the output switch handle (Q002) lights Now the green lamp (H003) above the bypass switch handle (Q003) lights too Only the green lamp (H003) above the bypass switch handle (Q003) lights Display shows 10. Press 11. Press 12. Press 13. Press 14. Press 15. Press on the keyboard or on the keyboard until Bypass operation : YES Bypass operation : NO

8.

Turn the output switch (Q002) to position ,,1"

9.

Turn the bypass switch (Q003) to position ,,0"

on the keyboard on the keyboard on the keyboard on the keyboard

Normal operation load power xx% No lamps on the bypass panel light any longer

7OA0001 GB rev.09

User Guide DP300E

13

Service Bypass Switch
7.2 Operating the external service bypass switch for parallel systems
Bypassing the parallel UPS system

Service Bypass Switch Mains
Q003

7.2.1
Load

Action Point 1-4 can be carried out with any of the parallel systems, however this will switch all systems into bypass operation. Display shows

Q001a

Q001b

Q002b

Q004 Q002a

1. 2.

Press Press Press Press

on the keyboard or on the keyboard until Bypass operation : NO Bypass operation : YES

DP300E

3.
DP300E

on the keyboard on the keyboard

4.

All systems will transfer to bypass operation Do not switch off any of the UPS systems until point 5-8 has been carried out

Bypass operation

Lamp indication on bypass panel 5. Check lamp indication on the bypass panel The green lamp (H003) above the bypass switch handle (Q003) lights The green lamp (H004) above the output isolator (Q004) and the green lamps (H002) above the output switch handles (Q002) light The green lamp (H002) above the output isolator light Only the lamp (H002) above the output switch handles (Q002) lights now Display shows 9. Warning: If the UPS is out of service for more than 8 days the connected batteries might be damaged. Refer to total ,,Switching off" as described in Instal. Guide Chapter 7.0. Open the front door and press both the green ,,ON" and the red ,,OFF" key simultaneously in any of the systems The acoustic alarm sounds for 30 secs.* Repeat for (all) other system(s).

6.

Turn the external bypass switch (Q003) to position ,,1"

7.

Turn the output isolator (Q004) to position "0"

8.

Turn all output switches (Q002) to position ,,0"

**System OFF**

10. Turn all input switches (Q001) to position ,,0" The red alarm LED below the display lights and the acoustic alarm sounds for 30 secs. * The acoustic alarm can be reset by the key

7OA0001 GB rev.09

14

User Guide DP300E

Service Bypass Switch
EMERGENCY (UPS not alive) 1. 2. 3. 4. 5. Turn the input switches (Q001) to position ,,0". Turn the output switches (Q002) to position ,,0". Turn the output isolator (Q004) to position "0". Change possible released system input fuse(s). Turn the bypass switch (Q003) to position ,,1".

7OA0001 GB rev.09

User Guide DP300E

15

Service Bypass Switch
7.2.2 Switching the parallel system from external bypass into normal UPS operation

Service Bypass Switch Mains
Q003

Load

Action 1. Check that output isolator (Q004) is in position "0" Turn input switches (Q001) and output switches (Q002) to position "1" Open the UPS front door and press the green "ON" key on all systems Point 4-7 can be carried out with any of the parallel systems, however this will switch all systems to bypass operation

Display shows

Q004

Q001a

Q001b

Q002b

Q002a

2.

**System OFF** Normal operation load power 0%

3.
DP300E

DP300E

Note: If battery has been disconnected please refer to "Starting Up" in Instal. Guide Chapter 5.0 to connect battery(-ies) again.

4. 5. 6. 7.

Press Press Press Press

on the keyboard or on the keyboard until Bypass operation : NO Bypass operation : YES

on the keyboard on the keyboard

All systems will transfer to bypass operation

Bypass operation

Lamp indication on bypass panel 8. Check that green lamp (H004) above output isolator (Q004) lights Turn the output isolator (Q004) to position "1" Now also the green lamp (H003) above the bypass switch handle (Q003) lights Only the green lamp (H003) above the bypass switch handle (Q003) lights

9.

10. Turn the bypass switch (Q003) to position ,,0"

Point 11-16 must be carried out with same UPS as was used for point 4-7

7OA0001 GB rev.09

16

User Guide DP300E

Service Bypass Switch
Display shows 11. Press 12. Press 13. Press 14. Press 15. Press on the keyboard or on the keyboard until Bypass operation : YES Bypass operation : NO Normal operation load power xx% No lamps on the bypass panel lights any longer

on the keyboard on the keyboard on the keyboard

7OA0001 GB rev.09

User Guide DP300E

17

Service Bypass Switch
7.2.3 Isolating one UPS for service/maintenance In a redundant system one UPS can be isolated for service/maintenance without affecting the other parallel UPS(s).
Service Bypass Switch Mains
Q003

1.
Load

Check that the remaining UPS(s) will be able to carry the load when one UPS is isolated. Switch off the system to be isolated for maintenance by pushing both the green "ON" and the red "OFF" key simultaneously. Disconnect battery, mains, and output by opening battery MCCB/fuse and turning input switch (Q001) and output switch (Q002) to position "0". When Q002 is in position "0" the UPS can be operated and tested as a single system without affecting the other parallel UPS(s).

Q004

2.

Q001a

Q001b

Q002b

DP300E

Q002a

3.

Switching back the UPS to normal parallel/redundant operation
DP300E

1. 2.

Turn the input switch (Q001) and the output switch (Q002) to position "1". Charge capacitors, connect battery and start up the UPS as described in chapter 5.0. The UPS will automatically switch to normal operation and start load sharing with the other parallelled UPS(s).

Warning! The system will discharge builtin capacitors. However, before working on the system check with a multimeter that there is no dangerous voltage on the terminals .

7OA0001 GB rev.09

18

User Guide DP300E

Preventive maintenance
8.0
8.1

Preventive maintenance
General

The maintenance of the UPS systems should be carried out by trained service engineers. We recommend that you sign a service and maintenance contract.

8.2 8.3

Fan Battery

It is recommended to replace the fans every 3rd year.

Systems with built-in batteries have as standard a battery monitoring feature (option in other systems). Every time automatic cyclic or manual check is activated, the condition of the battery is checked. The result is one of following: 1. Battery is OK - nothing will happen 2. Battery has reduced capacity - "Battery week" is given 3. Battery capacity far to low - "Battery defective" is given The battery monitoring test is performed by taking out max. 25% of the energy in the battery. But if the battery monitor is not installed or the exact present back-up time has to be checked, a battery capacity test (8.4) is recommended at least every sixth month. For safety reasons battery tests should preferably be made during uncritical periods for the loads connected. Test the battery capacity / condition from the keyboard as follows:

7OA0001 GB rev.09

User Guide DP300E

19

Preventive maintenance
8.4 Battery capacity test Note: Expect 16 hours recharge time after a battery capacity test before full backup time is available.
Actions 1. Press 2. Press or until Battery capacity test : xxx "xxx" is back-up time from last test ­ if no previous test has been performed or if the test has been aborted the display will show "???"! A battery monitor test can be performed in the same way by selecting "Battery monitor test" in the display. However, this test will not start, unless the battery is fully charged. The next step starts up the test! To abort press . Display shows Description

3. Press

Battery capacity test : ON

Starts the battery test. (To interrupt a running test ­ perform point 1-2 and then press key ) and

4. Press

Data stored Battery operation time : xxx min.

5. Wait about 1 sec.

6. Wait until backup Normal operation times expires and load power xx% a short alarm sounds. (No alarm in battery monitor test if battery is OK) 7. Press Battery capacity test : xxx

"xxx" is actual obtained back-up time in minutes. (Battery capacity test only). Exits the battery capacity test. If not operated the system will automatically exit this program after 30 seconds.

Warning: The UPS must at least be in operation for min. 16 hours in a 3 month period to ensure that the battery is sufficiently charged. If not the battery might be damaged.

8. Press

Normal operation load power xx%

If the UPS has to be taken out of operation for a period of time it is recommended to disconnect the battery in order to prevent it from being totally discharged. The information how to do this can be found in the installation guide.

7OA0001 GB rev.09

20

User Guide DP300E

Economy Operation
9.0
9.1

Economy operation
General

In economy operation the load is supplied directly from the mains, however the UPS is monitoring the mains and the output voltages and will in case of mains failure switch to battery operation without interruptions. The system will in order to keep the batteries fully charged at all times switch to normal operation in a pre-programmed sequence. The operation of the system is the same as already described in this guide with the exception of the following points: When starting up, the system will at first go into normal operation to ensure a fully charged battery, but will then switch into bypass after the programmed time (8-10 hours).

Note: When using economy mode there is NO power factor correction on the input, cabling dimensions should therefore be checked.

7OA0001 GB rev.09

User Guide DP300E

21

Software
10.0 Software
10.1 Choice of software
The CD is devided into two main parts: - DP-SOFT CDX : for serial communication - DP-SOFT+ : for parallel communication (e.g. for MLU-box) Installation: See software guide included on the CD.

10.2

Configuration code at normal operation

(Regarding test, see further information in guide included on the CD).

Oper. system Config. code

UNIX 3

VMS 3

Win3.1x 8

Win95 8

WinNT 8

OS/2 8

Novell 8

10.3

Choice of cable
Software DP-SOFT CDX DP-series DP300E Cable 0.801.179

Operating system Windows 3.1x Windows 95 Windows NT OS/2 Novell UNIX VMS Windows 3.1x Windows 95 Windows NT OS/2 Novell UNIX VMS

DP-SOFT+

DP300E

0.801.178

DP-SOFT+

DP300E

0.801.177

7OA0001 GB rev.09

22

User Guide DP300E

How to contact Silcon
11.0 How to contact Silcon

For further information: E-mail: [email protected] Homepage: http://WWW.silcongroup.com

AUSTRIA Silcon Elektronik GmbH Hausberggasse 1 A-7212 Forchtenstein Tel: +43 26 26 8 38 40-0 Fax: +43 26 26 8 35 64 CHINA Silcon (Qingdao) Power Electronics Co. Ltd. 1 Loushan Road CN-Qingdao P.C. 266043 Tel: +86 - 532 4810148 Fax: +86 - 532 4810147 DENMARK Silcon Power Electronics A/S Silcon Allé DK-6000 Kolding Tel: +45 - 75 54 22 55 Fax: +45 - 75 54 27 89 GERMANY Silcon Elektronik GmbH Industriestrasse 59a Postfach 2233 D-40764 Langenfeld Tel: +49 - 2173 9239-0 Fax: +49 - 2173 25977 GREAT BRITAIN Silcon Electronics Ltd. Milton Court, Bredbury Industr. Park Horsfield Way Stockport GB Cheshire SK6 2SU Tel: +44 - (0) 1614 066 866 Fax: +44 - (0) 1614 066 867

IRELAND Gotec Ltd. Clonshaugh Industrial Estate IE-Dublin 17 Tel: +353 - (1) 848 6033 Fax: +353 - (1) 848 6040 POLAND Silcon Poland Ltd. ul. E. Orzeszkowej 5 PL-02-374 Warzaw Tel: +48 - 82 26 59 75 01 Fax: +48 - 82 22 23 66 46 SWEDEN Silcon Power Support AB Box 20195 S-161 02 Bromma Tel: +46 - 8 29 02 90 Fax: +46 - 8 28 33 53 SWITZERLAND Gutor Electronics Ltd. Tägerhardstrasse 90 CH-5430 Wettingen Tel: +41 - 56 437 34 34 Fax: +41 - 56 437 34 44 THE NETHERLANDS Silcon B.V. Pieter Lieftinckweg 8 NL-1505 HX Zaandam Tel: +31 - 75 681 4 681 Fax: +31 - 75 681 4 682

7OA0001 GB rev.09

User Guide DP300E

23