Text preview for : HH03GB02.PDF part of APC DP100 Series Install Manual APC DP100 Series



Back to : HH03GB02.PDF | Home

DATAPOWERTM
DP100E Series
Installation Guide - (7HH0003 GB)

Copyright © 1997 Silcon Power Electronics A/S Due to continuous product development information given in this manual is subject to change without notice

7HH0003GB rev 02

Installation Guide DP100E

1

7HH0003GB rev 02

2

Installation Guide DP100E

Contents
1.0 Introduction 2.0 Unpacking 3.0 Placing
3.1 3.2 Storage System dimensions

4.0 Installation
4.1 4.2 4.3 4.4 4.5 Check of electrical data Electrical connections External connections Mains fuses and cable dimensions Main diagram

5.0 Start and operation of the system
5.1 5.2 Start up procedure LED indications

6.0 Programming parameters
6.1 6.2 6.3 DATAPOWERTM/Economy mode Other setting possibilities DIP-switch setting

7.0 Switching OFF 8.0 ComPortTM 9.0 Options/Accessories
9.1 9.2 9.3 9.4 9.5 9.6 MultiComTM (25 pins SUB-D male) Remote LED panel/EPO-portTM Remote LED panel Service bypass panel Transformer modules Battery modules

10.0 Software
10.1 Choice of software 10.2 Configuration codes 10.3 Choice of cable

11.0 How to contact Silcon

7HH0003GB rev 02

Installation Guide DP100E

3

Introduction
1.0 Introduction
The information given in this installation guide is of general nature for the local authorized electrical installer. By the installation national and local electrical regulations have as well to be adhered to. A DATAPOWER is an electronic equipment and must be treated accordingly. It is of the utmost importance that the installation and start-up procedure are carried out in a safe way so that no persons or equipment are injured.

7HH0003GB rev 02

4

Installation Guide DP100E

Unpacking
2.0 Unpacking
Enclosed in the package is an unpacking instruction.

7HH0003GB rev 02

Installation Guide DP100E

5

Placing
3.0 Placing
· The DATAPOWER has been constructed for indoor use in office environments or computer rooms. Ambient temperature must be 0-30°C (15-25°C is ideal for the batteries). Above 25°C battery lifetime is reduced. Relative air humidity must be from 30% to 90% not condensing. Sufficient cooling has to be ensured by a free space of min. 150mm from the ventilation slots on the back and 200mm from the ventilation slots on the right side. Avoid to place the system to direct exposure of sunlight.

·

· ·

·

Fig. 3.0.1: Free space from back

Fig. 3.0.2: Free space from side

3.1

Storage

If the DATAPOWER is not taken into use immediately, it must be stored in a dry, clean room at normal room temperature (20°C). The DATAPOWER should only be stored with fully charged batteries, so the system should be put input operation every 3rd to 6th month for no less than 12 hours, in order to recharge the built-in battery.

7HH0003GB rev 02

6

Installation Guide DP100E

Placing
3.2 System dimensions

Cubicle 3 Front view Side view

315

50

600

Cubicle 2 Front view Side view

50 50 565 615

315

50

600

7HH0003GB rev 02

Installation Guide DP100E

768

818

7

Placing
Top view

50

600

315 Bottom view 254 30,5

50

50 89,5

150,5

150,5

89,5 50

20

7HH0003GB rev 02

8

Installation Guide DP100E

30,5

Only battery modules

Installation
4.0 Installation
The installation examples in chapter 4.0 are for a standard DP100E.

4.1

Check of electrical data

Check the identification label on the back of the system to verify that the specified voltage and power rating match the available mains voltage and load requirements.

4.2
WARNING: Make sure that mains supply is switched off before any installation is carried out on the system. NOTE: Due to the leakage current of >3,5mA the DATAPOWER must always be grounded according to local regulations. WARNING: It is very important to follow the description, as you are working with hazardous DC voltage.

Electrical connections

The electrical connections and service on the system must be carried out by an authorized electrician according to national and local regulations. To get access to the terminals remove the screws on the cover, slide the cover upwards, dismount the earth connection, and remove the cover.

4.3

External connections

As a standard the DATAPOWER is made for 1 phase connection. Fig. 4.3.1:

Unscrew screw and demount cover

7HH0003GB rev 02

Installation Guide DP100E

9

Installation
Fig. 4.3.2:

7HH0003GB rev 02

10

Installation Guide DP100E

Installation
4.4 Mains fuses and cable dimensions
Standard system

Fig. 4.4.1:

System 3kVA 4kVA 5kVA 6kVA 8kVA 10kVA

Mains fuse (Fm) 20A 25A 35A 40A 50A 63A

Input cable UPS 3 x 4 mm2 3 x 6 mm2 3 x 10 mm 3 x 16 mm
2

Output cable UPS 3 x 4 mm2 3 x 4 mm2 3 x 6 mm2 3 x 10 mm2 3 x 10 mm2 3 x 16 mm2

3 x 10 mm2
2 2

3 x 16 mm

Input cable UPS Mains

Output cable UPS Load

7HH0003GB rev 02

Installation Guide DP100E

11

Installation
Fig. 4.4.2: Standard system with isolating transformer 230/230V

System 3kVA 4kVA 5kVA 6kVA 8kVA 10kVA

Mains fuse (Fm) 20A 25A 35A 40A 50A 63A

Input cable transformer 3 x 4 mm2 3 x 6 mm2 3 x 10 mm 3 x 16 mm
2

Input cable UPS 3 x 4 mm2 3 x 6 mm2 3 x 10 mm 3 x 16 mm
2

Output cable UPS 3 x 4 mm2 3 x 3 mm2 3 x 6 mm2 3 x 10 mm2 3 x 10 mm2 3 x 16 mm2

3 x 10 mm2
2

3 x 10 mm2
2

3 x 16 mm2

3 x 16 mm2

Input cable TR

Input cable UPS

Output cable UPS

Mains

Load

7HH0003GB rev 02

12

Installation Guide DP100E

Installation
Fig. 4.4.3: Standard system with isolating transformer 400/230V

System 3kVA 4kVA 5kVA 6kVA 8kVA 10kVA

Mains fuse (Fm) 16A 16A 20A 25A 35A 40A

Input cable transformer 3 x 2,5 mm2 3 x 2,5 mm2 3 x 4 mm
2

Input cable UPS 3 x 6 mm2 3 x 6 mm2 3 x 10 mm 3 x 16 mm
2

Output cable UPS 3 x 4 mm2 3 x 4 mm2 3 x 6 mm2 3 x 10 mm2 3 x 10 mm2 3 x 16 mm2

3 x 6 mm2 3 x 10 mm
2

3 x 16 mm2
2

3 x 10 mm2

3 x 16 mm2

Input cable TR

Input cable UPS

Output cable UPS

Mains

Load

7HH0003GB rev 02

Installation Guide DP100E

13

Installation
Fig. 4.4.4: Standard system with Service Bypass Panel (SBP)

NOTE: The DP100E Series must only be connected to the service bypass panel (SBP100E) manufactured by Silcon. If other service bypass panels but those manufactured by Silcon are used, the UPS system may be damaged and the warranty given by Silcon is repealed.

System 3kVA 4kVA 5kVA 6kVA 8kVA 10kVA

Mains fuse (Fm) 20A 25A 35A 40A 50A 63A

Input cable SBP 3 x 4 mm2 3 x 6 mm2 3 x 10 mm 3 x 16 mm
2

Input cable UPS 3 x 4 mm2 3 x 6 mm2 3 x 10 mm2 3 x 10 mm2 3 x 16 mm2 3 x 16 mm2

3 x 10 mm2
2

3 x 16 mm2

System 3kVA 4kVA 5kVA 6kVA 8kVA 10kVA

Output cable Output fuse Output cable UPS SBP (Fo) SBP 3 x 4 mm2 3 x 4 mm2 3 x 6 mm
2

16A 20A 25A 32/35A 40A 50A

3 x 4 mm2 3 x 4 mm2 3 x 6 mm2 3 x 10 mm2 3 x 10 mm2 3 x 16mm2

3 x 10 mm2 3 x 10 mm
2

3 x 16 mm2

Input cable SBP

Output cable SBP

Mains

Load

Input cable UPS

Output cable UPS

7HH0003GB rev 02

14

Installation Guide DP100E

Installation
Fig. 4.4.5: Standard system with isolating transformer 230/230V and SBP

NOTE: The DP100E Series must only be connected to the service bypass panel (SBP100E) manufactured by Silcon. If other service bypass panels but those manufactured by Silcon are used, the UPS system may be damaged and the warranty given by Silcon is repealed.

System 3kVA 4kVA 5kVA 6kVA 8kVA 10kVA

Mains fuse (Fm) 20A 25A 35A 40A 50A 63A

Input cable transformer 3 x 4 mm2 3 x 6 mm2 3 x 10 mm 3 x 16 mm
2

Input cable SBP 3 x 4 mm2 3 x 6 mm2 3 x 10 mm 3 x 16 mm
2

Input cable UPS 3 x 4 mm2 3 x 6 mm2 3 x 10 mm2 3 x 10 mm2 3 x 16 mm2 3 x 16 mm2

3 x 10 mm2
2

3 x 10 mm2
2

3 x 16 mm2

3 x 16 mm2

System 3kVA 4kVA 5kVA 6kVA 8kVA 10kVA

Output cable Output fuse Output cable UPS SBP (Fo) SBP 3 x 4 mm2 3 x 4 mm2 3 x 6 mm
2

16A 20A 25A 35A 40A 50A

3 x 4 mm2 3 x 4 mm2 3 x 6 mm2 3 x 10 mm2 3 x 10 mm2 3 x 16mm2

3 x 10 mm2 3 x 10 mm
2

3 x 16 mm2

Input cable TR

Input cable SBP

Output cable SBP

Mains

Load

Input cable UPS

Output cable UPS

7HH0003GB rev 02

Installation Guide DP100E

15

Installation
Fig. 4.4.6: Standard system with isolating transformer 400/230V and SBP

NOTE: The DP100E Series must only be connected to the service bypass panel (SBP100E) manufactured by Silcon. If other service bypass panels but those manufactured by Silcon are used, the UPS system may be damaged and the warranty given by Silcon is repealed.

System 3kVA 4kVA 5kVA 6kVA 8kVA 10kVA

Mains fuse (Fm) 16A 16A 20A 25A 35A 40A

Input cable transformer 3 x 2,5 mm2 3 x 2,5 mm2 3 x 4 mm
2

Input cable SBP 3 x 6 mm2 3 x 6 mm2 3 x 10 mm 3 x 16 mm
2

Input cable UPS 3 x 6 mm2 3 x 6 mm2 3 x 10 mm2 3 x 16 mm2 3 x 16 mm2 3 x 16 mm2

3 x 6 mm2 3 x 10 mm
2

3 x 16 mm2
2

3 x 10 mm2

3 x 16 mm2

System 3kVA 4kVA 5kVA 6kVA 8kVA 10kVA

Output cable Output fuse Output cable UPS SBP (Fo) SBP 3 x 4 mm2 3 x 4 mm2 3 x 6 mm
2

16A 20A 25A 35A 40A 50A

3 x 4 mm2 3 x 4 mm2 3 x 6 mm2 3 x 10 mm2 3 x 10 mm2 3 x 16mm2

3 x 10 mm2 3 x 10 mm
2

3 x 16 mm2

Input cable TR

Input cable SBP

Output cable SBP

Mains

Load

Input cable UPS

Output cable UPS

7HH0003GB rev 02

16

Installation Guide DP100E

Installation
4.5 Main diagram

7HH0003GB rev 02

Installation Guide DP100E

17

Start and operation of the system
5.0 Start and operation of the system
5.1 Start up procedure
The DATAPOWER can be operated by any person with no prior knowledge of a UPS system. When the mains and the load cables are connected to the DATAPOWER, it is started simply by: · Switching on the MCB (F1) on the rear side. The DATAPOWER will perform a self-check-procedure ending with the LED display showing red/yellow/green meaning that everything is OK. Switch on the button on the front of the DATAPOWER. The acoustic alarm will give a little beep when output power is available. Switch on the load.

·

·

The DATAPOWER will always be shipped with fully charged batteries, but due to transport and possible storage time the energy content of the batteries might not be 100% (indicated by a yellow LED bar). When installed it is recommended to test the system. See user manual.

5.2

LED indications

The LED indications are described in the user guide.

7HH0003GB rev 02

18

Installation Guide DP100E

Programming parameters
6.0 Programming parameters
The function of the DATAPOWER DP100E can be programmed either by a service computer or by DIP-switches. For changing the factory setting, please contact your local dealer.

6.1

DATAPOWERTM/economy mode

The DATAPOWER DP100E can be programmed to run in two different modes with different advantages. DATAPOWER mode: Is the true on-line mode, where the output is stabilized and the mains current is sinusoidal. Efficiency is above 95%. To achieve additional savings, the DATAPOWER DP100E can be programmed to run in economy mode. In economy mode the load is supplied directly from mains. In this mode the inverter is stand-by giving a very high efficiency. However, the DATAPOWER DP100E is monitoring the mains and the output voltage and will in case of mains failure uninterruptedly switch into battery operation. The DP100E is as standard set for DATAPOWER operation.

Economy mode:

6.2
·

Other setting possibilities
Voltage. Factory setting: 230V. Can be set for 220V, 230V, and 240V. Frequency. Factory setting: 50Hz. Can be set for 50Hz or 60Hz. Reserve tank. Factory setting: Inactive. If active about 75% of the stored energy is used during first failure and 25% is saved for a new failure. If not active all 100% energy is used first time. Automatic start. Factory setting: Active. Starts up after 1 minute. If active the DATAPOWER will restart, when mains return, if shut down was made because of low battery voltage or remote shut down. (If shut down was made because of overload or overtemperature the DATAPOWER has to be restarted manually). If not active the DATAPOWER has always to be restarted manually. Remote shut down (RSD). Factory setting: Active. If active the connected computer can switch off the UPS, when the programme termination has been completed. If not active the DATAPOWER will not accept RSD.

·

·

·

·

7HH0003GB rev 02

Installation Guide DP100E

19

Programming parameters
· RSD level. Factory setting: Low to high. Due to different standards the RSD can accept a shut down signal "high to low" or "low to high". RSD timer. Factory setting: 30 secs. When the computer has sent the RSD signal, it needs some time to terminate the running programme. By switching this can be programmed to 30 secs. or 2 min. By service computer it can be changed from 1 sec. to 10 min. Audible alarm level. Factory setting: Low. Can be set to high or low.

·

·

6.3

DIP-switch setting

The DIP-switch setting must be carried out by an authorized electrician. The DATAPOWER must be switched off before setting the DIP-switch. Otherwise the new setting will not be active. Access to the DIP-switch: a. b. c. d. e. Switch off the DP100E on the ON/OFF button on the front. Switch off main supply. Dismount the screws on the back. Draw back the cover and remove it. Set the DIP-switch, placed as shown below, to the wanted parameters. DIP-switch setting 1 2 3 4 5 6 7 8
ON OFF

Fig. 6.3.1:

SW1

X1B

X2B

Alarm level ON = Low OFF = High 50Hz/60Hz ON = 60Hz OFF = 50Hz DATAPOWER mode / economy mode ON = Economy OFF = DATAPOWER 4. Reserve tank ON = Active OFF = Inactive 5. Automatic restart ON = ON OFF = OFF 6. RSD ON/OFF ON = ON OFF = OFF 7. RSD level ON = High to low OFF = Low to high 8. RSD timer ON = 120 secs. OFF = 30 secs. SW1: Change between +5V and +12V on relay port (X5) pin 12 X1B: For remote display and EPO X2B: For RS232
7HH0003GB rev 02

1. 2. 3.

20

Installation Guide DP100E

Switching off
7.0 Switching off
Switching off the DATAPOWER must be done in the following way:

a. Switch off on the ON/OFF button.
b. c. Switch off mains fuse F1 on the rear. Switch off main supply.

7HH0003GB rev 02

Installation Guide DP100E

21

ComPortTM
8.0 ComPortTM
The ComPortTM can be used for communication purposes. To use this facility a data cable and some software are needed. This software can give warning to users and initiate a computer shut down in case of mains failure of longer duration. Finally the computer can complete the process by switching off the DATAPOWER. DP-SOFT CDX and cables are included as standard. The ComPortTM includes four potential free contacts and a remote shut down input. Fig. 8.0.1: MultiComTM

ComPortTM

7HH0003GB rev 02

22

Installation Guide DP100E

ComPortTM
DATA Relay contacts: Voltage: Current: 42VAC / 60VDC Max. 500mA Min. 500µA

Fig. 8.0.2: Relay contacts 14 NC 1 15 NC 1 2 COM 1 UPS off UPS on Common

16 NC 2 17 NC 2 4 COM 2

Normal operation Bypass / economy mode Common

18 NC 3 19 NC 3 6 COM 3

Normal operation Battery operation Common

20 NC 4 21 NC 4 8 COM 4

Battery voltage normal Battery voltage low Common

12+ 11 Pull up 24 GND

+5V or +12V depends on switch setting (SW1)

13+ Remote shut down input 25 -

7HH0003GB rev 02

Installation Guide DP100E

23

ComPortTM
UPS on UPS off Bypass / economy mode Normal operation Battery operation Normal operation Battery voltage low Battery voltage normal Galvanic isolated DC supply 5V / 30mA or 12V / 20mA Pull up resistor 2400ohm Remote shut down input High: 3,5V to 25V Low: -25V to 0,5V Min. pulse length: 1 sec. Pin 2 - 15 short circuit Pin 2 - 14 short circuit Pin 4 - 17 short circuit Pin 4 - 16 short circuit Pin 6 - 19 short circuit Pin 6 - 18 short circuit Pin 8 - 21 short circuit Pin 8 - 20 short circuit Pin 12 = PSU+ Pin 11 = Pull up + Pin 2 - 14 open circuit Pin 2 - 15 open circuit Pin 4 - 16 open circuit Pin 4 - 17 open circuit Pin 6 - 18 open circuit Pin 6 - 19 open circuit Pin 8 -. 20 open circuit Pin 8 - 21 open circuit Pin 24 = PSU GND

Pin 13 = RSD+

Pin 25 = RSD-

7HH0003GB rev 02

24

Installation Guide DP100E

Options/Accessories
9.0 Options/Accessories
When installing any option, turn the system off and switch off mains supply. Remove the cover to access the option mounting area of the DP100E. All optional printed circuit boards (PCB) are mounted at the top rear end of the unit. At any time during installation please observe that proper ESD handling precautions are maintained, since all optional PCB's contain static sensitive devices. When installation of options has been completed, mount the cover. Restore mains supply, and turn the unit on.

9.1

MultiComTM (25 pins SUB-D male)

As standard one piece of MultiComTM is mounted. However, the DATAPOWER can be equipped with up to 2 additional pieces of RS232/V.24 serial MultiComTM interfaces. Via the serial communication ports a lot of information from the DATAPOWER can be shown "on-screen" on the connected computer. Furthermore the RS232/V.24 interface can be connected to a service computer and parameters and standard settings can be changed. Installation of one MultiComTM interface Remove the cover shield for MultiComTM (2) and (3) and break it, so that it can be used for covering the MultiComTM (3) socket hole. See figure 9.1.1. Fig. 9.1.1: Cover shield (3) (2)

·

Place the RS232/V.24 interface into the MultiComTM (2) socket hole and fasten it by using the two 3 x 8 mm screws and washers, position no. 001, 002, and 003 as shown in figure 9.1.3. Program the address decode DIP-switch (S001) on the RS232/V.24 interface to address 2. See table 1. Connect and place the ribbon cable (34 pins), position no. 005, between the DATAPOWER Controller, connector X2B, and the RS232/V.24 interface, connector X2B by using the first connector of four on the ribbon cable. See figure 9.1.3. The two M3 x 20 mm spacer bolts, position no. 004, shall not be used when installing one MultiComTM interface.

·

·

7HH0003GB rev 02

Installation Guide DP100E

25

Options/Accessories
Fig. 9.1.2: DIP-switch

Fig. 9.1.3:

Connections

·

Place the earth wire between connection on chassis plate and X003 on MultiComTM interface. The RS232/V.24 interfaces need no further configuration in the system, since the DATAPOWER Controller tests, whether any RS232/V.24 interface(s) is (are) connected and active during initialization of the main programme.

Installation of two or more MultiComTM interface · Remove the cover shields for all the MultiComTM interfaces, which have to be installed. Break the cover shield(s) and remount it (them) over the socket(s), which remain unused, if not all four interfaces have to be installed. See figure 9.1.1. Place the RS232/V.24 interfaces into the corresponding MultiComTM socket holes and fasten them by using either two 3 x 20mm spacer bolts, pos. no. 004, or the two 3 x 8mm screws and washers, pos. no. 001, 002, and 003, as shown in figure 9.1.3. Use the spacer bolts for MultiComTM (2) and (3), if MultiComTM (3) has to be installed. Otherwise, if only MultiComTM (2) has to be installed, use only the screws and washers. Place the earth wires between connection on chassis plate and X003 on the numbers of the MultiComTM interfaces, which have been mounted. Program the address decode DIP-switch (S001) on each RS232/V.24 interface to the corresponding address. See figure 9.1.2 and table 1.

·

·

·

·

Table 1: S001.1 MultiComTM (2) MultiComTM (3) OFF OFF S001.2 ON OFF S001.3 OFF ON S001.4 OFF OFF

7HH0003GB rev 02

26

Installation Guide DP100E

Options/Accessories
· Connect and place the ribbon cable (34 pins), pos. no. 005 between the DATAPOWER Controller, connector X2B and connector X2B on all the RS232/ V.24 interfaces, which have to be installed as shown in figure 9.1.3. Note that only one ribbon cable has to be used.

Table 2: Pin 2 Pin 3 Pin 7 · TXD/103 RXD/104 SG/102 Transmitted data Received data Signal ground

Program the DATAPOWER to the numbers of MultiComTM interfaces, which have been mounted. Program in step 38, described in procedure 7.000.817, shown in chapter 9 in the service manual.

9.2

Remote LED panel/EPO-portTM

EPO-portTM (Emergency Power Off) can be connected to a stop switch so that the DATAPOWER can be switched off quickly e.g. in case of fire. Installation of EPO-portTM Remove the cover shield for the Emergency Power OFF. See figure 9.2.1. Fig. 9.2.1: Cover shield

·

Place the interface for the EPO interface into the socket hole for the 25 pole SUB-D plug and fasten the PCB on the two stand-offs using the two 3 x 8mm screws and washers. Connect and place the 10 pole ribbon cable with the 9 pole SUB-D to the connector X003 on the EPO interface. Fasten the 9 pole SUB-D plug with the two fastening plates with the two standoffs UN4-40 F. Fasten the fastening plates to rear panel with the two screws 4 x 1/4. Connect and place 14 pole ribbon cable between the DATAPOWER controller, connector X1B, and interface for LED panel /EPO, connector X001. Place the earth wire between connection on chassis plate and X004 on the EPOportTM.

·

· NOTE: Jumper J001 on the interface must be removed, if Emergency Power Off function has to be used. Jumper J001 on the interface must be mounted, if Emergency Power Off is not in use.

· ·

·

7HH0003GB rev 02

Installation Guide DP100E

27

Options/Accessories
Fig. 9.2.2: EPO-portTM (9 pins SUB-D female) 1 2 +5V 3 GND 4 EPO 5 GND 6 7 +5V 8 GND 9 EPO reset

Switching off: Pin 2 and 4 connected: Pin 2 and 4 disconnected:

DATAPOWER can be switched on. DATAPOWER switches off immediately.

Switching on: The DATAPOWER cannot start again before reset is established by connecting pin 2 and 4 again and resetting the DATAPOWER in one of the described ways: · · Connect pin 2 and 9 shortly Switch off the DATAPOWER on main switch on the front panel and then switch on again

7HH0003GB rev 02

28

Installation Guide DP100E

Options/Accessories
9.3 Remote LED panel
A remote LED panel unit with LEDs like the one on the front is available for remote monitoring. For that purpose a remote panel interface has to be mounted. This interface also contains the Emergency Power Off (EPO) and is installed as described in chapter 9.2. Installation of remote LED panel Cable for LED panel has to be a 18 wire multicable, e.g. 18 x 0,14mm2. In the end of the cable for connection to DATAPOWER, a 25 pole SUB-D male has to be used. In the end for connection to LED panel, a 25 pole SUB-D female has to be used. In the SUB-D plugs pin 1 has to be connected to pin 1, pin 2 to pin 2, and so on, until pin 18 to pin 18. The 25 pole SUB-D female plug on the cable has to be mounted inside the box for LED panel. Dismount the cover for LED panel by dismounting the four screws on the backside of the LED panel. Inside the box, plug the 25 pole SUB-D plug into the socket on the LED-PCB. Place the grommet for hole on the multicable. Fix the grommet into the inlet on the box. Remount the cover and the four screws. Maximum length of the connection cable is 100m. The cables used must be shielded. Use SUB-D plugs of metal or metalized plastic and connect the shield to the cable relief clamp in the SUB-D plug connected to the DATAPOWER. The shield must not be connected to the SUB-D plug at the remote LED panel.

32mm
13mm

Fig. 9.3.1: Remote LED panel

Fig. 9.3.2: Mountig holes

7HH0003GB rev 02

Installation Guide DP100E

29

Options/Accessories
9.4 Service bypass panel
The bypass switch isolates the system so that service can be safely carried out without any interruption to the load. Fig. 9.4.1: Service bypass panel

NOTE: The DP100E Series must only be connected to the service bypass panel (SBP100E) manufactured by Silcon. If other service bypass panels but those manufactured by Silcon are used, the UPS system may be damaged and the warranty given by Silcon is repealed.

System Input

UPS SERVICE BYPASS SBP100E
Refer to User Guide for operation instructions

System Output

Q001
Only operate Q002 when H002 is ON

H002

Q002 Normal Bypass

NOTE: When the external manual bypass switch is switched from "Normal" to "Bypass" the output voltage is no longer adjusted or controlled by the DATAPOWER.

S002

350 mm

Press and hold S002 to request operation of Q002

UPS Input

This panel has two sources of power

UPS Output

WARNING: Before operating the external manual bypass panel check that the DATAPOWERTM is running in normal operation. When S002 is pushed, H002 must go on within 1 sec. - if not release S002 immediately bypass mains is outside tolerances and manual bypass switch cannot be operated.

400 mm

7HH0003GB rev 02

30

Installation Guide DP100E

Options/Accessories
Fig. 9.4.2: Mounting holes

4 x ų 6.5mm fixing holes

X001 SYSTEM INPUT

X004 SYSTEM OUTPUT

X010 X002 UPS INPUT

X003 UPS OUTPUT

Type SBP-105E SBP-110E

Maximum cable size 16mm2 16mm
2

Dimensions HxWxD 315 x 305 x 125 (175*) 350 x 400 x 125 (175*)

Weight 7 kg 11 kg

Fixing centres AxB 240 x 240 270x 330

* Depth of enclosure including switch handles. For fuse and cable sizes please refer to section 4.4.

7HH0003GB rev 02

Installation Guide DP100E

31

Options/Accessories
9.4.1 Service bypass panel diagram

7HH0003GB rev 02

32

250V

Installation Guide DP100E

Options/Accessories
9.5 Transformer modules
Two different modules with galvanic isolation transformer are available for the DATAPOWER 100E. The transformer module is used if the DATAPOWER 100E should have a three phase supply or if galvanic isolation is required. For fuse and cable sizes please refer to section 4.4. Signalling cable from thermo switch in trafo module and DATAPOWER 100E included. Power cable between trafo module and DATAPOWER 100E for systems installed without external service bypass panel included.

7HH0003GB rev 02

Installation Guide DP100E

33

34
Connections:
TRANSFORMER MODULE Mains Input L1 N/L2 L N L N L N Output X001 X004 SERVICE BYPASS PANEL LOAD L N GND X003 L N Th. switch X002 L N X010 1 2 3 4 L N Input 1 2 3 4 MBS Control For external Tr. Th. switch DATAPOWER 100E L N Output

7HH0003GB rev 02

Options/Accessories

MAINS

L N/L PE

Installation Guide DP100E

Options/Accessories
9.6 Battery modules
Two different battery modules are available for extended autonomy time. Dimensions as shown in section 3.2. Cables for interconnection between battery module and DATAPOWER 100E are included.

7HH0003GB rev 02

Installation Guide DP100E

35

Options/Accessories
Connections:

DATAPOWER 100E

BATTERY MODULE

Ext. Battery + 384VDC

+ Battery 384VDC WARNING! HIGH VOLTAGE

For external batt. temp. sensor

Temp. sensor

WARNING! HIGH VOLTAGE Only qualified electricians are allowed to perform the installation and the service of
the battery modules. Safety precautions for working with high voltage have to be kept. Lead-acid batteries must be separated from equipment and disposed of as notifiable waste.

7HH0003GB rev 02

36

Installation Guide DP100E

Software
10.0 Software
10.1 Choice of software
The CD is devided into two main parts: - DP-SOFT CDX : for serial communication - DP-SOFT+ : for parallel communication (e.g. for MLU-box) Installation: See software guide included on the CD.

10.2 Configuration code at normal operation
(Regarding test, see further information in guide included on the CD).

Oper. system

UNIX

VMS Alpha Vax 1

VMS Win3.1x Win95 WinNT Other 3 8 8 8

OS/2

Novell

Config. code

3

8

8

10.3 Choice of cable
Operating system Windows 3.1x Windows 95 Windows NT OS/2 Novell UNIX Windows 3.1x Windows 95 Windows NT OS/2 Novell UNIX VMS Software DP-SOFT CDX DP-series DP100E Cable 0.801.179

DP-SOFT+

DP100E

0.801.178

DP-SOFT+

DP100E

0.801.177

7HH0003GB rev 02

Installation Guide DP100E

37

How to Contact Silcon
11.0 How to contact Silcon

For further information: E-mail: [email protected] Homepage: http://WWW.silcongroup.com

AUSTRIA Silcon Elektronik GmbH Hausberggasse 1 A-7212 Forchtenstein Tel: +43 26 26 8 38 40-0 Fax: +43 26 26 8 35 64 CHINA Silcon (Qingdao) Power Electronics Co. Ltd. 1 Loushan Road CN-Qingdao P.C. 266043 Tel: +86 - 532 4810148 Fax: +86 - 532 4810147 DENMARK Silcon Power Electronics A/S Silcon Allé DK-6000 Kolding Tel: +45 - 75 54 22 55 Fax: +45 - 75 54 27 89 GERMANY Silcon Elektronik GmbH Industriestrasse 59a Postfach 2233 D-40764 Langenfeld Tel: +49 - 2173 9239-0 Fax: +49 - 2173 25977 GREAT BRITAIN Silcon Electronics Ltd. Milton Court, Bredbury Industr. Park Horsfield Way Stockport GB Cheshire SK6 2SU Tel: +44 - (0) 1614 066 866 Fax: +44 - (0) 1614 066 867
7HH0003GB rev 02

IRELAND Gotec Ltd. Clonshaugh Industrial Estate IE-Dublin 17 Tel: +353 - (1) 848 6033 Fax: +353 - (1) 848 6040 POLAND Silcon Poland Ltd. ul. E. Orzeszkowej 5 PL-02-374 Warzaw Tel: +48 - 82 26 59 75 01 Fax: +48 - 82 22 23 66 46 SWEDEN Silcon Power Support AB Box 20195 S-161 02 Bromma Tel: +46 - 8 29 02 90 Fax: +46 - 8 28 33 53 SWITZERLAND Gutor Electronics Ltd. Tägerhardstrasse 90 CH-5430 Wettingen Tel: +41 - 56 437 34 34 Fax: +41 - 56 437 34 44 THE NETHERLANDS Silcon B.V. Pieter Lieftinckweg 8 NL-1505 HX Zaandam Tel: +31 - 75 681 4 681 Fax: +31 - 75 681 4 682

38

Installation Guide DP100E