Text preview for : APC Smart SUA RT 3KVA TO 10KVA.pdf part of APC SU10000 Serviece manual for UPS APC 3-10kVA



Back to : APC Smart SUA RT 3KVA TO | Home

Service Manual English




APC Smart-UPS® RT
3,000VA ­ 10,000VA 200-240 Vac
Tower/Rack Mount
Uninterruptible Power Supply




SURT 3kVA-10kVA Service Manual 1
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Table of Contents

1 Safety Precautions........................................................................................................................................... 3
2 Introduction to SURT...................................................................................................................................... 4
2.1 Key Points ........................................................................................................................................... 4
2.2 One-Line Diagram .............................................................................................................................. 4
2.3 Main Circuit Components ................................................................................................................... 4
2.4 Functional Description ........................................................................................................................ 5
2.5 Power Train Operation........................................................................................................................ 5
2.6 Transistor-Level Diagrams ................................................................................................................. 6
3 User Interface ................................................................................................................................................ 11
3.1 Front Panel Display and Control Buttons ......................................................................................... 11
3.2 Terminal Mode.................................................................................................................................. 13
3.3 SmartSlot Accessories (Webcard)..................................................................................................... 15
4 Installation..................................................................................................................................................... 16
5 Component Replacements............................................................................................................................. 16
6 Troubleshooting ............................................................................................................................................ 17
6.1 Unit Setup ......................................................................................................................................... 17
6.2 Required Tools .................................................................................................................................. 17
6.3 Visual Inspections ............................................................................................................................. 17
6.4 Troubleshooting Flowchart ............................................................................................................... 18
6.5 Diode Checks .................................................................................................................................... 20
6.6 Documenting Failures ....................................................................................................................... 25
7 ECO's ............................................................................................................................................................ 25
8 Test After ECO's ........................................................................................................................................... 26
Appendix A. Fault codes on LED display & stored in EEPROM .................................................................... 28
Appendix B. ECO list as of October, 2005....................................................................................................... 33




SURT 3kVA-10kVA Service Manual 2
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
1 Safety Precautions

Read and adhere to the following warnings when installing or servicing a UPS and/or battery packs.
Failure to observe these warnings may result in serious injury, death or damage to the equipment.
WARNINGS · Do not attempt to install or service external batteries alone. A qualified
electrician should perform the installation and servicing of external
batteries.
· Disconnect charging source(s) BEFORE connecting or disconnecting
battery terminals.
· External batteries may retain lethal voltages after power has been
disconnected and all switches are off.
· Use extreme caution when making terminal connections. Do not allow
cables to touch anything except the intended terminal.
PRACTICES Always wear:
· Goggles or face shields
· Acid-resistant, insulated gloves
· Protective aprons
· Protective overshoes or rubber boots
Always use:
· Insulated tools
· Rubber mats to cover batteries during servicing
· Rubber mats or rubber stands on the floor
· Adequate lifting devices
Remove:
· Watches, rings, and other metal objects from your body
PRECAUTIONS · To avoid static build-up, service personnel should establish a grounding
contact prior working on batteries.
· Do not lay tools or metal parts on top of batteries.
· Lead-acid batteries contain hazardous, toxic materials.
§ Do not open, alter or mutilate batteries. Internal materials may be
harmful to the skin and eyes.
§ Do not dispose of batteries in a fire. There is danger of explosion.
· Handle, transport and recycle batteries in accordance with local codes
and regulations.




SURT 3kVA-10kVA Service Manual 3
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
2 Introduction to SURT
2.1 Key Points
· Double-conversion online topology
· Inverter voltage is selectable through communication only: 200V, 208V, 220V, 230V, 240V.
· Bypass "acceptable voltage" window changes with Inverter voltage setting.
· Batteries must be connected to start UPS. After startup, batteries can be safely removed and replaced
without interruption to the output.
· Lynx2 (3kVA ­ 6kVA) has single battery (192V nominal) referenced to output Neutral.
· Lynx3 (7.5kVA ­ 10kVA) has two battery strings (+192V and -192V nominal) managed independently and
charged with separate chargers.
· Lynx3 (7.5kVA ­ 10kVA) can accept single-phase or three-phase input voltage. In both cases, Bypass is only
single-phase ("L1" and "N" inputs) so the input wiring must be sized to handle full-load current as single-
phase.

2.2 One-Line Diagram




160 -284
VAC Input
Input
Filter Inverter
Rectifier &
Section +/- DC Bus Output
PFC
Section

Bypass
Switch 240 VAC
Output
Battery
Charger




192 VDC
Battery



2.3 Main Circuit Components
The primary sections of the UPS are:
· Input disconnect and filter stage
· Input Power Factor Correction (PFC) power stage
· Energy storage stage (dc bus capacitor bank)
· Output power stage (inverter)
· Bypass
· Battery charger
· Battery: 1 or 2 strings each connected to output Neutral




SURT 3kVA-10kVA Service Manual 4
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
2.4 Functional Description
The control of power module and fault detection logic is uP based. The input filter stage contains input backfeed relays,
input EMI filter, transient suppression, and battery select transfer relays. Input PFC power stage contains non-isolated
power factor correcting AC/DC converters. PFC converter is split in two power sections ­ positive and negative boost
stage ­ while operating on-line and in positive boost and buck boost power stage while operating on battery. This
converter is capable of full power operation from 160 to 280 VAC line to neutral or from a nominal DC battery voltage of
192VDC. The output from this stage is a +/-395V center tapped dc bus. The energy storage stage is split DC bus
capacitor handling seamless transitions from battery to line and vice versa as well as the low and high frequency power
stages ripple. The inverter stage operates directly from +/- 395VDC bus and produces an AC output voltage of
200/208/220/230/240Vac (for NAM and EMEA) or 200Vac (for Japan). The output of the UPS is either connected through
a pair of relays either to the inverter or to the input filtered line. The UPS contains 1 or 2 battery chargers, each rated
400W.


2.5 Power Train Operation
When operating on line, the input voltage is first rectified so two half wave rectified voltage waveforms are produced in
reference to the Neutral. Positive line rectified signal is fed to positive boost PFC stage. This stage is a boost type
converter which converts positive half rectified input signal into DC positive bus voltage of +395V, drawing the input
current in phase with positive half cycle of the line current. The boost stage consists of an input choke, high frequency
IGBT switch, high frequency soft recovery diode and the output electrolytic capacitor. The positive boost stage is
bypassed by a low power diode which serves as the boost converter protection in the case of sudden line overshoots and
overvoltages or any other condition which causes input line peak voltage to be higher than DC bus capacitor voltage. The
negative line rectified signal is fed to negative PFC stage. This stage is also boost type converter and operates in the
same manner as the positive PFC boost stage. This stage converts negative line half rectified voltage to negative DC bus
voltage of -395V. The bottom line is that when operating on line both PFC stages are operating as boost converters each
processing half of the total output power per phase.

When operating on battery, the transfer relays connect the PFC to a DC voltage from the battery. The battery voltage is
fed through a filter and inrush stage to both positive and negative PFC stages. The battery filter consists of chokes and
two electrolytic capacitors. The function of the filter is to prevent high frequency ripple from PFC stage going back to
battery and to provide differential mode filter for high frequency noise emanating from battery buses or cables (in case of
external battery packs). The inrush stage as its name says during startup limits the battery inrush current. When the
battery is connected to the input of the PFC stage, the battery filter capacitor and positive DC bus capacitor charging
current is limited through two 50 ohm PTC resistors. When capacitors are charged to battery voltage inrush relays are
switched into closed position bypassing the PTC resistors. The positive PFC stage operates as a DC/DC boost converter
and converts battery voltage to DC bus voltage. The operation in this mode is the same as operation on line as described
above, except that current drawn from battery is now DC current. The negative PFC stage operates as buck boost stage
and converts battery voltage to negative DC bus voltage.

The output stage of the UPS consists of inverter with output filter and bypass relays. This stage is a DC/AC converter
which function is to convert DC bus voltages into regulated output sine wave voltage. The inverter uses a neutral point
clamp topology and consists of the top and bottom section. The top section converts positive DC bus voltage of 395V into
positive half wave sine voltage and bottom portion converts negative DC bus voltage into negative half sinewave voltage.
The PWM control of inverter regulates the frequency and amplitude of the output AC voltage. The output filter consists of
a smoothing choke and a filter capacitor. The filtered voltage is fed through a NO relay contact to the UPS output.




SURT 3kVA-10kVA Service Manual 5
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
2.6 Transistor-Level Diagrams

Lynx2: 3kVA ­ 6kVA

D22



Input 160-280Vac LINE


K3 L8
BATTERY D14
L101 Q11



BATTERY 192V
50 OHM


Q12//Q13
50 OHM
C12//C13
Q2//Q3


L4+L5+L6
D23
K1
C27//C28
C6//C8




Q14//Q15


D24



Q6//Q7 Q4//Q5


Q16


L7 D15
BATTERY



LINE K4


D19 Lynx II POWER TRAIN




SURT 3kVA-10kVA Service Manual 6
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
SURT 3kVA-10kVA Service Manual 7
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Lynx3: 7.5kVA ­ 10kVA (interleaved PFC)
Bypass




Input 160-280Vac LINE
50/60Hz



BATTERY
BATTERY
50 OHM
+192V

50 OHM Inverter output
200-240Vac
50/60Hz




NEUTRAL




BATTERY
-192V




BATTERY




LINE

Lynx3 POWER TRAIN




SURT 3kVA-10kVA Service Manual 8
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Lynx3 PFC power board, 640-0761 ­ Circuit locations




SURT 3kVA-10kVA Service Manual 9
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Lynx3 INVERTER power board, 640-0762




SURT 3kVA-10kVA Service Manual 10
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
3 User Interface
3.1 Front Panel Display and Control Buttons
The front panel contains status and diagnostic LEDs and two control buttons. Several of the LEDs comprise bar
graphs that display status and diagnostic information according to the table below.

Load Smart-UPS RT Front Display Battery Charge




Indicator Description
Online The Online LED illuminates when the UPS is drawing utility power and
performing double conversion to supply power to connected equipment.
On Battery The UPS is supplying battery power to the connected equipment.

Bypass The Bypass LED illuminates indicating that the UPS is in bypass mode.
Utility power is sent directly to connected equipment during bypass mode
operation. Bypass mode operation is the result of an internal UPS fault, an
overload condition or a user initiated command either through an accessory
or the manual bypass switch. Battery operation is not available while the
UPS is in bypass mode. Refer to Troubleshooting in this manual.
Fault The UPS detects an internal fault.
Refer to Troubleshooting in this manual.
Overload An overload condition exists. See Troubleshooting.

Replace The battery is disconnected or must be replaced. See Troubleshooting.
Battery


Table 1. Front Panel LEDs.




SURT 3kVA ­ 10kVA Service Manual 11
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Feature Function
Power On Press this button to turn on the UPS. (See below for additional capabilities.)

Power Off Press this button to turn off the UPS.

Cold Start
When there is no utility power and the UPS is off, press and hold the
button to power up the UPS and connected equipment.
The UPS will emit two beeps. During the second beep, release the button.
Self-Test Automatic: The UPS performs a self-test automatically when turned on, and
every two weeks thereafter (by default). During the self-test, the UPS briefly
operates the connected equipment on battery.
Manual: Press and hold the button for a few seconds to initiate the self-
test.
Table 2. Front Panel Control Pushbuttons.




Diagnostic Utility The UPS has a diagnostic feature that displays the utility
Voltage voltage applied to the UPS.

The UPS starts a self-test as part of this procedure. The self-
test does not affect the voltage display.
Press and hold the button to view the utility voltage bar
graph display. After a few seconds the five-LED, Battery Charge
display on the right of the front panel shows the utility input
voltage.
Refer to the figure at left for the voltage reading (values are not
listed on the UPS).
The display indicates the voltage is between the displayed
value on the list and the next higher value.




Table 3. Front Panel Bar Graphs.




SURT 3kVA ­ 10kVA Service Manual 12
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
3.2 Terminal Mode
SURT can be configured in a number of ways: Network Management Card web interface, PowerChute ® Software,
Terminal Mode, or UPS-Link commands.
To access Terminal Mode, you will need:
- A computer with an RS-232 serial port
- A terminal application such as Hyperterminal
- An APC black cable 940-0024C (included with the UPS)

Make sure that no SmartSlot accessory is installed in the SmartSlot bay of the UPS. The SmartSlot
prevents access to certain UPS communication features such as the Terminal Mode.

Using a standard APC serial cable (APC part number 940-0024C), connect the computer serial
port to the back of the UPS.

Open a terminal program. Hyperterminal example:
From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.




The "Connection Description" dialog
box appears. Enter a name for this
connection and select any icon for
it.


Click [OK]




The "Connect To" dialog box
appears. In the "Connect using"
drop-down list select the COM port
you're going to use to communicate
with the UPS.
If you get a message that this port
is used by another application then
either use a different COM port or
close the application using the
intended port.
Click [OK]




SURT 3kVA ­ 10kVA Service Manual 13
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
In the communication settings
dialog box, select the following
settings:
Bits per second: 2400
Data bits: 8
Parity: Note
Stop bits: 1
Flow control: None


Click [OK]




Press the Enter key. The root terminal mode menu will appear, similar to the following:




To configure the UPS, press the 1 key. The UPS will chirp and the "UPS Settings" menu will appear.




SURT 3kVA ­ 10kVA Service Manual 14
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
To change a setting, press the corresponding key (not case-sensitive) and follow the instructions.

Please note that if no key is pressed for approximately 5 minutes, the Terminal Mode session will time out and you'll have
to press Enter and start from the root menu again.



3.3 SmartSlot Accessories (Webcard)

SURT models include a standard SmartSlot that is compatible with accessories used in other APC products.

Notes on "event log" entries in the AP9619 (NMC or "webcard"):
· Almost all internal UPS faults are recorded as "Bad output voltage" regardless of whether or not the
detected fault is related to the Inverter or Bypass. The NMC is not able to differentiate between the
different UPS failure codes.
· "Battery charger failure" could be a momentary battery overvoltage condition -- see if this alarm is cleared
within 2 seconds in the log.




SURT 3kVA ­ 10kVA Service Manual 15
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
4 Installation
See User Manual included with the UPS for installation precautions and instructions.

Installation troubleshooting: Make sure:
· each battery string is above 175V (there are two battery modules per string)
· all battery modules are securely connected
· input AC is connected correctly, input phase_select switch set correctly to 1 or 3 (if exists)
· input breaker closed (if exists)
· output breakers on (if exist)



5 Component Replacements
Replacement boards:
SKU Power Board Control Board
SURT3000 0P7510 0P7603
SURT5000 0P7510 0P7600
SURT6000 0P7516 0P7606


SKU PFC power Inverter power Main Control Aux Control Bias & I/O
SURT7500 0P7611 0P7621 0P7507 0P7631 0P7641
SURT8000 0P7611 0P7621 0P7608 0P7631 0P7641
SURT10000 0P7611 0P7621 0P7501 0P7631 0P7641

Battery modules (RBC44?) ­ one for Lynx2, two for Lynx3?

Bezels w/ stickers

Display PCB/bezel assemblies

Fan for Lynx2
Fan for Lynx3

Battery fuses: (515-1030A)

See ??? for optional PDU's including H/W kit for Lynx2 output




SURT 3kVA ­ 10kVA Service Manual 16
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
6 Troubleshooting
Safety: Remove jewelry, pendants and wrist watches.


6.1 Unit Setup
Unpack the UPS and put it on a flat even surface (mind OSHA regulations). Check the packaging for any signs of
damage.

Lynx2
Net Weight 120.00 lbs. ( 54.55 kg)

Shipping Weight 140.00 lbs. ( 63.64 kg)




Note: Follow all environmental regulations. Discard old batteries in an environmentally friendly way. Be sure to deliver
spent batteries to a recycling facility or ship to the manufacturer in the replacement battery packing material.

6.2 Required Tools
· Digital multimeter (for example, Fluke 87)
· Power resistor to discharge capacitors
· Serial communication cable (RS-232)
· Communication software (for example, laptop and "Hyperterminal" software in Windows)
· Phillips screwdriver
· AC power supply
· Load


6.3 Visual Inspections

Visual inspection is often overlooked but is one of the most important steps in diagnosing a problem. It can also
save a lot of time.

Exterior
Check the packaging and exterior of the UPS for any physical damage
1. Plastic bezels
2. Fan guard & blades
3. Bent sheet metal
4. PDU breakers

Interior
Check all wiring, connections, and PCB components
1. Wire insulation broken
2. Burned components and/or burned marks on PCB
3. Daughter PCBs not tight in sockets
4. Components touching chassis or other components (esp. small heatsinks, power resistor leads)
5. Leads not clipped properly, solder-bridges (solder-side of PCB)




SURT 3kVA ­ 10kVA Service Manual 17
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
6.4 Troubleshooting Flowchart


Start



Visual inspection
(exterior)


Make sure all battery
packs disconnected




Each No Replace battery
Battery pack
pack(s)
>84V?

Yes




Remove top panel,
Discharge all caps




Visual inspection
(interior)




No
Diode Repair & record
checks OK? failed parts


Yes




Connect Battery,
Push ON-Switch


Lynx 2: Check
D781, D782, D776, D777,
Brains on? No Troubleshoot D778, D779, Q712
(Fan on) LPS Lynx 3: Check D704, D705,
D706, D707, D714, D718,
D722, Q704
Yes




(next
page)




SURT 3kVA ­ 10kVA Service Manual 18
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
(continued)




Disconnect SNMP SURT
Yes cable from ctrl bd. Evaluate CTRL-U Faults
Fault
Send Y response and LED display. Table
displayed?
Send 1...1 See "SURT Faults Table"
Send CTRL-U
No




Check PFC:
No Lynx 2: D716-k to J712: +400V No
Does unit +/-400V bus Troubleshoot
D715-a to J712: -400V
cold start? voltages OK? PFC
Lynx 3: PGND to +400V
PGND to -400V
Yes
Yes



Apply AC input voltage

Troubleshoot Lynx2: Check Q708,
Inverter Q709, Q710, Q711,
Q726, Q727, D748,
Troubleshoot D749, D723
Does unit go No input voltage Lynx3: Check IC903,
on-line ? sense and IC904
transfer relays
Lynx 2: Check Q705,
Yes
Q706, Q715, Q716,
Q717, Q718, D750,
D751
Lynx 3: Check
Does unit stay on IC1403, IC1404,
No Troubleshoot
with all batteries IC1407, IC1408
Charger collector-emitter and
disconnected?
gate-emitter

Yes



Lynx 2: Check Q730, Q731, F703,
F704, D736, D737, D738, D739.
Re-connect batteries
Lynx 3: Check Q1407, Q1408,
F1401, F1402, D1406, D1407,
D1408, D1409


Does unit No
hold load on
battery?
SURT
Yes Faults
Table

Apply ECO's



Record failure type,
Calibrate and Test unit list all failed parts along Done
with part markings




SURT 3kVA ­ 10kVA Service Manual 19
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
6.5 Diode Checks
The following "good value" measurements were made with a functional board and a Fluke 87 DMM. These
measurements are approximate and will vary depending on the meter used. See the power board diagram on the
next page for Test Point locations.

Lynx2: 3kVA - 6kVA
Good
+ Probe - Probe Components checked If open If short
Value
Fuse




F701, F702 (battery Both fuses bad, PFC
BATT BATTF zero OK
fuses) probably has problem

+VIN +400V 0.4V D716, D748 at least 1 part bad

VMID +VIN 0.45V Q709, Q710, D706 all parts bad at least 1 part bad
PFC




-400V -VIN 0.4V D715, D723 all parts bad at least 1 part bad

-VIN B+ 0.45V Q726, Q727, D707 all parts bad at least 1 part bad

-VIN VMID zero RY704-normally closed RY704 bad OK

Q706 and
INV_OUT +400V 0.8V Q706, Q715, Q716 at least 1 part bad
Q715/Q716 bad
charges if < 2V, Q718 or Q717 At least D751 and 1
INV_OUT VMID D751, Q718, Q717
Inverter




> 2V bad IGBT bad
charges if < 2V, Q715 or Q716 At least D750 and 1
VMID INV_OUT D750, Q715, Q716
> 2V bad IGBT bad
Q705 and
-400V INV_OUT 0.8V Q705, Q718, Q717 at least 1 part bad
Q718/Q717 bad
Charger output




VMID CHGR_SEC 0.45V D738, D739 at least 1 part bad

CHGR_SEC CHGR_L 0.45V D736, D737 at least 1 part bad

CHGR_L BATTF 0.45V D735 D735 bad

Q712 bad, check F705, Q729, D714, and
VMID LPS_FET 0.55V Q712
Bias Supply




output diodes

VMID +24V_SW 0.5V D782 D782 bad, check Q712, F705, Q729, D715

VMID +15V_SW 0.5V D781 D781 bad, check Q712, F705, Q729, D714

ZERO-
B+ 0.6V D731, TH701, TH702 D731 bad, check TH701, TH702
Zero off




OFF_FET
ZERO-
OFF_FET
BATTF 0.85V Q728 Q728 bad, check MV703, GDT701




SURT 3kVA ­ 10kVA Service Manual 20
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
SURT 3kVA ­ 10kVA Service Manual 21
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Lynx3: 7.5kVA through 10kVA
Good
+ Probe - Probe Components checked If open If short
Value
Fuses bad, +PFC
+BATT +BATTF zero F1403, F1404, OK
Fuses




probably has problem
Fuses bad, -PFC
-BATT -BATTF zero F1405, F1406 OK
probably has problem

+VIN_P1 +400V 0.35V D903, IC903 (at least)
D903, D905,
IC903, and/or IC904 bad
+VIN_P2 +400V 0.35V D905, IC904 (at least)

-400V -VIN_N1 0.35V D902, IC903 (at least)
D902, D904,
IC903, and/or IC904 bad
-400V -VIN_N2 0.35V D904, IC904 (at least)
PFC




PGND +VIN_P1 0.4V IC903 (at least)

PGND +VIN_P2 0.4V IC904 (at least)
IC903 and/or IC904 bad
-VIN_N1 PGND 0.4V IC903 (at least)

-VIN_N2 PGND 0.4V IC904 (at least)

-400V INV_OUT 0.35V
IC1407, IC1408 IC1407 and/or IC1408
Inverter




INV_OUT +400V 0.35V

INV_OUT PGND Open IC1403, IC1404 IC1403 and/or IC1404 bad

+Charger F1402 open, Q1407
Charger




+400V 0.55V Q1407, F1402 Q1407 bad
Out probably bad
-Charger F1401 open, Q1408
-400V 0.55V Q1408, F1401 Q1408 bad
Out probably bad




SURT 3kVA ­ 10kVA Service Manual 22
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Lynx3 PFC power board, 640-0761




IC903, IC904 =

SURT 3kVA ­ 10kVA Service Manual 23
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Lynx3 INVERTER power board, 640-0762




IC1403, IC1404 = IC1407, IC408 =.

SURT 3kVA ­ 10kVA Service Manual 24
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Notes:
Cold boot the unit and get the diagnostic information from the serial port before it gets cleared
out. If the unit fails right away, read the display LED pattern and the failure code.

Initial power up (brains up) with batteries only
Check calibration of batteries (both strings), DC buses, firmware version, model #, serial number, etc.
Check fault history (^U command)
Cold-boot
check calibration of DC buses, output AC voltage, etc.
AC-input
check calibration of AC input voltage
disconnect batteries to see if unit shuts down (indicates charger failure)
ON & OFF buttons, BYPASS switch, etc.
Startup with AC-input
Load: add/remove/calibration of watts & VA
AC input: add/remove with load
HF-OFF check

· Bypass switch
· 3phase input switch selection
· Lynx3 Battery voltage commands: ^J for +battery, ^K for ­battery in PROG mode
· Once failed part is identified, try to determine if there were any manufacturing defects that might
have caused the part to fail: Insufficient torque on mounting screw, leads not clipped, solder-bridge,
parts touching other components, etc.
· In Terminal Mode, if Model = "??", the EEPROM has probably become cleared or corrupted.
· "Overload" fault (ctrl-u = 02) is stored during factory testing (during production). Seeing this fault
stored in a field unit does not necessarily mean the overload timeout happened at the customer's site.
· "EQ charge" is normal in later versions of Lynx2 & Lynx3 firmware. If the battery voltage ever drops
below 200V, the charger will go up to 235V for at least 5 minutes before settling back down to 218V.
EQ charge is also performed about once every 4 weeks.l


6.6 Documenting Failures
Int'l Stars, SIEBEL, or local spreadsheets. Make sure to record all relevant information about the diagnosis:
· Reference designators of failed parts with date codes and vendor marks
· PCB revisions, firmware revisions, accessories added, etc.
· Recommend Corrective Actions and/or PCB revisions as needed.



7 ECO's
See ECO RMA database. For list as of this revision, see Appendix B.
· Need table showing which PCB revision combinations can be used together (examples: 762x requires 763x
or later, 1kVA change)
· Need list of PCB revisions that are ok to ECO and send back to customers
· Need table showing which PCB revisions need which ECO's




SURT 3kVA ­ 10kVA Service Manual 25
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
8 Test After ECO's
(Final test fixture)
All calibration
Cold-boot
AC input: add/remove
Add load, check calibration of Voutput, Wout, VAout, DC buses, Vbatt, ...
AC input: add/remove
With AC input, disconnect batteries
HF-OFF check




SURT 3kVA ­ 10kVA Service Manual 26
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Failure Analysis Report
& Corrective Action Plan

Customer RMA number
Customer location RMA date
Report date PCB1 s/n Rev
Model PCB2 s/n Rev
Unit s/n Accessory1 s/n Rev

Initial Assessment Yes No Additional Information
Does the unit cold boot? ___ ___
Does the unit indicate a fault? ___ ___
Does unit operate online with no faults? ___ ___
Is there any output? ___ ___
Does unit switch to bypass? ___ ___
Do all display leds work? ("A" in SM) ___ ___
Does unit operate under 100% load? ___ ___
Unit shut off after 9 min on battery standby? ___ ___

Physical damage (deformed metal or plastic, loose connections, cut insulation, poor crimps, etc.)




Voltages: Pos Bus Neg Bus Vin Vout Charger (no batt) f/w rev Fault History
Command: Ctrl G* Ctrl H* Shift L Shift O Shift B or ^J / ^K* b Ctrl U*
Displays
Measured n/a n/a

Voltages 5V 12V -12V -15V 15V 24V Vbat (list packs separately)
Measured

Action Taken to Repair



Repaired Unit - Measured and Calibrated Voltages
Voltages Pos Bus Neg Bus Vin Vout Charger (batteries disconnected) Fault History
Command Ctrl G* Ctrl H* Shift L Shift O Shift B or Shift J / K* (Lynx 3) Ctrl U*
Displays
Measured n/a

Corrective Actions to be Taken



Additional Notes



*in programming mode 2/14/2005



SURT 3kVA ­ 10kVA Service Manual 27
©2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced,
photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the
copyright owner. www.apc.com Rev 2005-2
Appendix A. Fault codes on LED display & stored in EEPROM
Display LEDs show "1" for LED ON and "0" for LED OFF in the Battery capacity bar graph. For example, the following display indicates "Battery Capacitor
Soft Start Fault".




Notes
All values provided in UPS-Link terms. Overload test uses % power (watts) or % VA, whichever is greater.
The last fault(s) detected can be retrieved by sending the "Ctrl-U" command in Programming mode.
Display Ctrl- Auto-Recover from Related
Fault Action Taken Repair suggestion
LEDs U FAILURE_BYPASS? ECOs
Confirm battery voltage(s) above
165V and that +/-400V buses rise
to within 15V(9V) of the battery
bus(es) within 12 seconds and. If
they don't, check voltage after soft-
0 start PTCs, relay and relay drives.
1
Battery Capacitor The unit immediately changes state to Can't be in
1 11 Lynx2: TH701. TH702, RY702, BM934
Soft Start Fault UPS_FAILURE (less than 1ms) FAILURE_BYPASS
0 Q701, Q728, F701, F702.
0
Lynx 3: TH1401, TH1402,
TH1403, TH1404, RY1403,
RY1404, RY1405, RY1406,